Basic Policy
It is University policy -to the maximum extent feasible by present earthquake engineering practice - to acquire, build, maintain, and rehabilitate buildings and other facilities which provide an acceptable level of earthquake safety, as defined in this policy, for students, employees, and the public who occupy those buildings and other facilities at all locations where University operations and activities occur. It is also University policy to repair University buildings and other facilities damaged in an earthquake as set forth below in the section entitled Repair of Buildings and Other Facilities Damaged by Earthquakes. Feasibility is to be determined by weighing the practicability and cost of protective measures against the gravity and probability of injury resulting from a seismic occurrence.
Responsibility.
The President is responsible for overall administration of this policy and shall provide for (1) interpretation or clarification of the policy as may be required; (2) development of seismic safety criteria, standards, and guidelines supplementary to the policy; (3) evaluation of seismic safety programs and review of specific proposals for the abatement of seismic hazards; and (4) determination of University-wide priorities among seismic safety projects and other projects proposed for inclusion in the Capital Improvement Program.
The President shall assign specific duties and authority to individuals within the Office of the President who may engage professional consultants or other specialists to advise and assist them in matters involving seismic safety.
The Chancellors, Senior Vice President-Business and Finance, Vice President-Agriculture and Natural Resources, Director-Lawrence Berkeley Laboratory, Director-Lawrence Livermore Laboratory, and Director-Los Alamos Scientific Laboratory are the officials responsible for taking all reasonable steps to assure protection of persons under their respective jurisdictions against the effects of earthquakes which could result in the loss of life or injury to persons. Each responsible official shall assign specific duties and authority to individuals under his or her jurisdiction for the purpose of discharging this responsibility.
Program for Abatement of Seismic Hazards.
Each responsible official shall develop a program for abatement of seismic hazards in existing buildings and other facilities within their respective jurisdictions and shall establish priorities for seismic safety projects in accordance with this policy. Each responsible official shall coordinate proposed seismic correctional work with (1) proposed fire protection work (see University policy on fire protection, issued September 22, 1971) [Editor's Note: In place of the aforementioned policy on fire protection, the University currently follows, as policy, fire protection regulations of CCR, Title 24, Part 9.], (2) other proposed work involving environmental health and safety considerations, and (3) reasonable and prudent rehabilitation for functional and programmatic improvements.
The program for abatement of seismic hazards shall include identification and temporary and permanent correction of potential earthquake falling, sliding, or rupturing hazards such as, but not limited to, interior and exterior building elements, utilities, equipment, fixtures, furnishings, and other contents which could be dislodged, fall, overturn, slide, or rupture during seismic disturbances. Temporary measures to reduce the risks of injury pending permanent corrective action shall be considered and implemented if feasible.
The Consulting Structural Engineer.
Each responsible official shall secure the services of one or more consulting structural engineers experienced in field investigations and analyses of damage in earthquakes. The consulting structural engineer shall be required to examine existing buildings and other facilities as directed by the responsible official and to submit to the responsible official reports on the adequacy of the resistance of such campus buildings and other facilities to seismic forces based on (1) conformance to the current seismic provisions of California Code of Regulations (CCR), Title 24, California Building Standards Code, or local seismic requirements (e.g., city or county building regulations), whichever requirements are more stringent; and (2) the consulting structural engineer's professional evaluation of their anticipated seismic performance, expressed in terms of Good, Fair, Poor, or Very Poor, as defined in Appendix A, with respect to degree of risk of injury to persons but not necessarily in conformance with the above specific seismic provisions. For buildings and other facilities which are reported as Poor or Very Poor by the consulting structural engineer, the responsible official shall immediately consider alternatives to undiminished continued use and occupancy of the buildings and other facilities, including total or partial evacuation, temporary emergency measures, reductions in use, reconstruction, or combinations of these alternatives, and shall then take appropriate action.
The consulting structural engineer shall be required to include in all reports recommendations regarding priorities for abatement of seismic hazards and estimates of costs for correcting seismic deficiencies in accordance with this policy.
Standards for Seismic Rehabilitation Projects.
When evaluation by the consulting structural engineer of existing buildings or other facilities discloses conditions which do not afford an acceptable level of safety, proposed correctional work shall be incorporated in the program developed by the responsible official for abatement of seismic hazards and integrated in the University's proposed Capital Improvement Program. Seismic rehabilitation projects shall provide, as a minimum, an acceptable level of earthquake safety based on the sole consideration of the protection of life and prevention of personal injury, insofar as predictable, at a level of safety equivalent to that which would be established by compliance with the current seismic provisions of CCR, Title 24, California Building Standards Code, or local seismic requirements, whichever requirements are more stringent, disregarding, insofar as possible, potential building damage not jeopardizing life, which would be expected from one earthquake of the intensity of at least IX on the Modified Mercalli Intensity Scale (modified by Charles F. Richter in 1958, as shown in Appendix B), except that an intensity of VIII can be utilized for buildings on the Davis and San Diego campuses. The intent of seismic rehabilitation shall be to reconstruct buildings and other structures so that they would have a Good seismic performance rating, as defined in Appendix A. based on the present state of the practice of earthquake engineering.
When funds for seismic rehabilitation are limited, the program developed by the responsible official may include a phased rehabilitation program for selected buildings. The first phase would have the goal of reducing the greatest life safety hazards of the structure such as reducing the potential of partial building collapse and/or reducing falling hazards at building entrances and along adjacent walkways. Later phases, to be performed when funds are available, would complete the seismic rehabilitation program of the structure. The consulting structural engineer shall assist the responsible official in establishing the scope of work in each phase of a phased rehabilitation program.
Preliminary plans for all seismic rehabilitation projects shall be reviewed by the consulting structural engineer, who shall verify the scope of the rehabilitation work and shall prepare any recommendations regarding any special criteria which should be considered in the project design. Upon completion of plans and specifications, the consulting structural engineer shall review the plans and structural calculations for completeness, general accuracy, appropriateness of details, and for compliance with any special criteria. The design structural engineer shall incorporate comments into the plans prior to bidding.
Repair of Buildings and Other Facilities Damaged by Earthquakes.
In addition to the requirements established elsewhere in the Policy pertaining to the construction, maintenance and rehabilitation of University buildings and facilities, the following standards shall apply to repair of University buildings and facilities which are damaged by earthquakes.
New Buildings and Other Facilities; Hospitals.
The design and construction of new buildings and other facilities on University premises shall, as a minimum, comply with the current seismic provisions of CCR, Title 24, California Building Standards Code, or local seismic requirements, whichever requirements are more stringent. In addition, provisions shall be made for adequate anchorage for seismic resistance of nonstructural building elements-including, but not limited to, glass, fixtures, furnishings, and other contents, equipment, material storage facilities, and utilities (gas, high-temperature water, steam, fireprotection water, etc.) - with respect to potential hazards to persons in the event of seismic disturbances.
New University buildings shall not be constructed on the trace of an active geological fault.
Preliminary plans for new major capital improvement projects, except pre-engineered buildings, wood-framed buildings of less than 3,000 square feet, and buildings not intended for human occupancy other than hospitals proposed for construction shall be examined by the consulting structural engineer, who shall prepare recommendations regarding any special criteria that, in that engineer's opinion, should be recognized in providing adequate resistance to seismic forces to minimize the risk of injury to persons and damage to property. Upon completion of the final plans, the consulting structural engineer shall review the plans and structural calculations for completeness, general accuracy, structural details, and for compliance with any special criteria previously established. Should seismic design standards be revised during the period between completion of final plans and the date of advertisement for bids, the consulting structural engineer shall review again the plans and structural calculations before advertising for bids. The design structural engineer shall incorporate all comments into the plans prior to bidding.
Prior to the release of funds for structures other than hospital or for seismic rehabilitation projects, a letter or report from the campus consulting structural engineer shall be submitted, stating that the construction plans are in general conformance with the University policy on seismic safety.
The design and construction of new facilities or alterations for hospitals, skilled nursing facilities, and intermediate-care facilities as defined in Section 15001 of the California Health and Safety Code, on University premises or under University operation shall comply with CCR, Title 24, California Building Standards Code.
University Policy on Seismic Safety
APPENDIX A
Meaning of GOOD, FAIR, POOR, OR VERY POOR SEISMIC PERFORMANCE RATINGS
GOOD seismic performance rating would apply to buildings and other structures whose performance during a major seismic disturbance* is anticipated to result in some structural and/or nonstructural damage and/or falling hazards** that would not significantly jeopardize life. Buildings and other structures with a GOOD rating would have a level of seismic resistance such that funds need not be spent to improve their seismic resistance to gain greater life safety, and would represent an acceptable level of earthquake safety.
FAIR seismic performance rating would apply to buildings and other structures whose performance during a major seismic disturbance* is anticipated to result in structural and nonstructural damage and/or falling hazards** that would represent low life hazards. Buildings and other structures with a FAIR seismic performance rating would be given a low priority for expenditures to improve their seismic resistance and/or to reduce falling hazards** so that the building could be reclassified GOOD
POOR seismic performance rating would apply to buildings and other structures whose performance during a major seismic disturbance* is anticipated to result in significant structural and nonstructural damage and/or falling hazards that would represent appreciable life hazards. Such buildings or structures either would be given a high priority for expenditures to improve their seismic resistance and/or to reduce falling hazards** so that the building could be reclassified as GOOD or would be considered for other abatement programs, such as reduction of occupancy.
VERY POOR seismic performance rating would apply to buildings and other structures whose performance during a major seismic disturbance* is anticipated to result in extensive structural and nonstructural damage, potential structural collapse, and/or falling hazards that would represent high life hazards. Such buildings or structures either would be given the highest priority for expenditures to improve their seismic resistance and/or to reduce falling hazards** so that the building could be reclassified GOOD or would be considered for other abatement programs such as reduction of occupancy.
** Falling Hazards are defined for the purposes of these seismic performance ratings as potential falling or sliding hazards such as interior and exterior building elements including parapets, ornamentation, chimneys, walls, and partitions, but excluding equipment, fixtures, ceilings, furniture, furnishings, and other contents. The falling hazards in the excluded list above should not be used in the determination of the seismic performance rating of a building or structure but should be abated.
University Policy on Seismic Safety
APPENDIX B
Definition of Masonry A, B, C, D:
Masonry A. Good workmanship, mortar, and design; reinforced, especially laterally, and bound together by using steel, concrete, etc.; designed to resist lateral forces.
Masonry B. Good workmanship and mortar; reinforced, but not designed in detail to resist lateral forces.
Masonry C. Ordinary workmanship and mortar; no extreme weaknesses like failing to tie in at the corners, but neither reinforced nor designed against horizontal forces.
Masonry D. Weak materials, such as adobe; poor mortar; low standards of workmanship; weak horizontally.
*** The version of the scale given above was published by Richter (1), and is a light abridgement of the original scale. Richter also included the description of the types of construction included here. The original scale was published in 1931 by H. O. Wood and Frank Neuman (2).